PVC Insulation, Multi-Triples, Layers, Collective Screen

Engineering Specifications
Standard:
BS 5308-2
Rated Voltage:
300/500 V
Conductor:
Stranded annealed plain copper
Insulation:
Polyvinylchloride TI1 to BS 6746
Assembly:
Cores twisted to form triples, twisted triples in concentric layers, and wrapped by polyester tapes.
Color code:
Black / White / Red, continuously numbered, or identification tapes numbered
Wrapping:
Polyester tapes Collective Screen
Aluminum polyester tape with tinned drain wire and wrapped by polyester tapes
Sheath:
Polyvinylchloride TM1 to BS 6746 colour black or grey or blue
Minimum bending radius:
7.5 x d (d= overall diameter)
Temperature rating:
+5oC up to +50oC during operation
Packing:
On non-returnable wooden drums
SKU: CPM4275 Categories: , ,

Description

Application
These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes.