pe_insulationsingle_or_triple_paircollective_screen-e1509336058650

PE Insulation, Mutlipairs, Layers and Individual

Engineering Specifications
Standard:
BS 5308-1
Rated Voltage:
300/500 V
Conductor:
Stranded annealed plain copper
Insulation:
Polyethelene 03 to BS 6234
Assembly:
Cores twisted to form pairs, pairs screened by aluminium polyester tapes, screened pairs twisted in concentric layer and
wrapped by polyester tapes
Color code:
Black / White, continuously numbered, or identification tapes numbered
Screen:
Collective screen of aluminum polyester tapes with tinned drain wire and wrapped by polyester tapes.
Bedding:
Polyvinylchloride
Armoring:
Galvanized steel wire armor to BS 1442
Sheath:
Polyvinylchloride TM1 to BS 6746 color black or blue
Minimum bending radius:
10x d (d= overall diameter)
Temperature rating:
+5oC up to + 50oC during operation
SKU: CPM4297 Categories: , ,

Description

Application
These cables are used in the chemical and petrochemical industries for the transmission of analogue and digital signals for measurements and process control purposes, where mechanical damages are expected to occur.